Oil immersed transformer

3D core transformer

General

 

 

FARADY S11-M.RL, S13-M.RL series of three-dimensional triangular wound core transformer breaking the traditional planar structure, use symmetrical three-phase three-dimensional structure, the product is completely symmetrical three-phase core magnetic circuit reluctance greatly reduced, excitation current and significantly reduce the unload loss,which is a use of traditional materials, 

but runs quieter, more compact energy-efficient transformers.

 Its energy saving, environmental protection material on the outstanding performance of the province, and in full compliance with the energy policy.

 

 

 


 

Standard

 

 

1.IEC60076-1: 1993 Power transformers 

2 GB1094.1-1996 power transformers 

3 GB6451-2008 oil-immersed power transformers technical parameters and requirements 

4 JB / T10088-2004 6kv-500kv power transformer sound level grade.

 

 

 


 

Product Features

 

 

1 .saving energy: 40-50% reduction in no-load loss, load loss reduction 7-10%; 

2. reduce line losses: No-load current is reduced more than 90%; 

3. ultra-quiet: 10-15 dB noise reduction; 

4. No interference: MFL reduced by more than 50%; 

5.conservation of raw materials: copper, iron cost reduction of 20-30%; 

6.significant economic benefits: variable costs fell 17.2 percent ten years than the new S9 style.

 

 

 


 

Service condition

 

a) Suitable for indoor or outdoor application

b)Air temperature:

Maximum temperature: +40℃; Minimum temperature:-30℃

c) Humidity:

Monthly average humidity 95%; Daily average humidity 90% .

d) Altitude above sea level:

Maximum installation altitude: 2000m.

e)Max wind speed:35M/s

f) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.

g) No frequent violent shake

Note: * Beyond those services condition should enquiry to manufacturer technical dept during order

 

 

 

 


 

Technical Specification

 

 

Type

 

Voltage combination

 

 

Vector group

Loss(W)

 

 

 

Impedance

 

%

 

 

Dimension

(L*W*H)

mm

 

 

Weight

(kg)

 

Primary

(KV)

 

Tapping range

 

Secondary

KV

No Load loss

Full

load loss

S13-MRL-30

 

 

6

6.3

6.6

10

10.5

11

13.2

13.8

15

 

 

 

 

 

 

 

±2x2.5%

 

 

 

 

 

 

0.4 or other

 

 

 

 

 

 

Yyn0 or

Dyn11

80

630

 

 

 

 

 

 

4.0

680*680*686

300

S13-MRL-50

100

910

690*690*686

360

S13-MRL-63

110

1090

730*730*796

500

 

S13-MRL-80

130

1310

730*730*816

600

 

S13-MRL-100

150

1580

780*780*950

700

 

S13-MRL-125

170

1890

950*950*1124

850

 

S13-MRL-160

200

2310

990*990*1164

950

 

S13-MRL-200

240

2730

1020*1020*1207

1100

 

S13-MRL-250

290

3200

1050*1050*1320

1250

 

S13-MRL-315

340

3830

1100*1100*1450

1550

 

S13-MRL-400

410

4520

1140*1140*1430

1850

 

S13-MRL-500

480

5410

1250*1250*1500

1900

 

S13-MRL-630

570

6200

 

 

 

6.0

1330*1330*1540

2200

 

S13-MRL-800

700

7500

1400*1400*1640

2750

 

S13-MRL-1000

830

10300

1450*1450*1690

3300

 

S13-MRL-1250

970

12000

1560*1560*1930

4000

 

S13-MRL-1600

1170

14500

1600*1600*1990

4400

 

Note: *The above parameter is only subject to our standard design, special requirement can be customized