Home >  Our Products > New Products >  Amorphous metal core
Amorphous metal core


Amorphous core transformer could lower electric energy loss to only 40% per day

No load loss of amorphous core transformers is only 25% of traditional transformer

Amorphous core distribution transformers reduce the impact on the global environment.

Good solution of energy conservation contributes to reducing CO2 emissions to recommend use amorphous transformer





inquiry
  • Description
  • Technical Specification
  • Comments

  • The amorphous core transformer built inside amorphous metal core is to convert H.V. electricity into L.V electricity for safe use.
    There is two difference loss of amorphous core transformers, Load loss and No load loss
    load losses caused by the load on the Amorphous Core Transformer during the use of electricity
    no-load losses (standby electricity) caused by Amorphous Core Transformers when there is no use of electricity
    Farady amorphous metal distribution transformer core significantly reduce no-load losses by using an amorphous metal core which could lower 75% No load loss compare to normal electrical transformer
  • Table 1: D13 Series with C.R.G.O wound Core

    Model
    Rated
    Capacity
    (kVA)

    Primary
    rating
    (V)

    Tapping
    Range(%)

    Secondary
    Rating
    (V)

    Loss(W)
    No load
    loss

    Load
    loss

    D13-3
    3
    34500/19920
    33000/17321
    20000/11547
    13200/7620
    11000/6350
    or others

    ±2x2.5%
    Or thers


    120-240
    240-480
    250-500
    Or thers

    9
    45
    D13-5
    5
    19
    75
    D13-10
    10
    36
    120
    D13-15
    15
    50
    195
    D13-25
    25
    80
    290
    D13-37.5
    37.5
    105
    360
    D13-50
    50
    135
    500
    D13-75
    75
    190
    650
    D13-100
    100
    210
    850
    D13-167
    167
    350
    1410
    D13-250
    250
    500
    2000
    D13-333
    333
    650
    2500
    Note: *The above parameter is only subject to our standard design, special requirement can be customized

    Table 2: DH16 Series with Amorphous Metal Core
    Model
    Rated
    Capacity
    (kVA)

    Primary
    rating
    (V)

    Tapping
    Range(%)

    Secondary
    Rating
    (V)

    Loss(W)
    No load
    loss

    Load
    loss

    DH16-3
    3
    34500/19920
    33000/17321
    20000/11547
    13200/7620
    11000/6350
    or others

    ±2x2.5%
    Or thers


    120-240
    240-480
    250-500
    Or thers

    8
    45
    DH16-5
    5
    8
    75
    DH16-10
    10
    12
    120
    DH16-15
    15
    15
    195
    DH16-25
    25
    18
    290
    DH16-37.5
    37.5
    30
    360
    DH16-50
    50
    32
    500
    DH16-75
    75
    45
    650
    DH16-100
    100
    50
    850
    DH16-167
    167
    65
    1410
    DH16-250
    250
    90
    2000
    DH16-333
    333
    120
    2500


    Overall size and weight


    Table 1: About D13 Series with C.R.G.O wound Core

    Rating voltage:13200/7620 or 11000/6350

    Model
    Rated
    Capacity
    (kVA)

    Overall size(mm)
    Weight(kgs)
    A
    B
    C
    D
    E
    Oil weight
    Total weight
    D13-3
    3
    760
    430
    530
    330
    286
    20
    105
    D13-5
    5
    780
    430
    530
    330
    30
    110
    D13-10
    10
    830
    430
    530
    330
    30
    130
    D13-15
    15
    850
    480
    580
    380
    40
    185
    D13-25
    25
    880
    500
    580
    410
    45
    210
    D13-37.5
    37.5
    930
    560
    640
    460
    60
    300
    D13-50
    50
    980
    560
    640
    460
    591
    70
    335
    D13-75
    75
    980
    680
    720
    554
    103
    460
    D13-100
    100
    1020
    780
    800
    610
    123
    530
    D13-167
    167
    1050
    830
    890
    660
    155
    670
    D13-250
    250
    1100
    960
    950
    660
    247
    950
    D13-333
    333
    1150
    960
    960
    660
    250
    1000

    Note: *The above overall size and weight is for reference only,Farady technical dept have right to modify without prior notify



Contact Us

+86-577-61722510

Our friendly customer service people are here to help you from 8.30am to 5pm Unique

Fax:+(86)-577-61777257

E-mail:info@farady.cn

Add:Su\\\'ao,Liushi,Yueqing,Zhejiang,P.R.China

Fast Register

  • By Registing you can download PDF on the website. take part in our monthly events receive emails from us!

Newsletter

  • Send me useful tips, industry articles and new product announcements (every month or so).

Top